Model 4064 is used for sensing limits of increasing or decreasing differentials. At the set differential, safety control system pressure coming into port A will vent out of port B. A typical application would be on a gas compressor installation. The gas discharge line would be connected to port P1, and the suction pressure line would be connected to port P2. If the pressure at P1 exceeded that of port P2 by the set amount, (indicating compressor connecting rod overloading), port A would vent and shut down the engine. Another application would be to sense excessive pressure drop through a filter, indicating filter cloggin